eTron Series · Utility-scale storage
5 MWh.One 20-foot unit.
SU5016E2500KC
Liquid-cooled LFP storage with 2.5 MW of power for 50 Hz grids.
- Nameplate capacity
- 5,016 kWh
- Nominal AC power
- 2.5 MW
- −30°C to +55°C rated
- IP55
Values from the current datasheet.
See what the numbers mean.
5 layers
Protection architecture
BMS, PCS and EMS integrated in a five-layer protection design.
314 Ah
LFP cells
Safe LFP chemistry in a 416S12P configuration.
20 ft
Plug-and-play unit
A standard 20-foot container, with mirrored -L/-R configurations.
Designed for grid-scale sites.
-
Intelligent liquid cooling
Keeps cells in their best temperature band for life and safety.
-
Multi-layer fire safety
Dry pipe, gas detection and ventilation, aerosol suppression and alarms.
-
IEC-certified for 50 Hz grids
Including Australia: IEC 62477-1, 62619, 63056, 62933 and more.
Built for heat and cold
Technical details, when you need them.
Specifications
System
- Nominal AC power
- 2,500 kW
- Nameplate capacity
- 5,015.96 kWh
- Communication
- Modbus TCP/IP
- Auxiliary power supply
- AC 400 V / 3P4L 50 Hz
Battery
- Chemistry
- LFP (lithium iron phosphate)
- Cell capacity
- 314 Ah
- Configuration
- 416S12P
- Nominal voltage
- 1,331.2 V
- Voltage range
- 1,123.2 – 1,497.6 V
Environment & protection
- Degree of protection
- IP55
- Operating temperature
- −30°C ~ +55°C (derating above 50°C)
- Relative humidity
- 0 – 95% RH
- Max working altitude
- 4,000 m
- Noise emission
- ≤ 80 dB @ 1 m
General
- Dimensions (W×H×D)
- 6,058 × 2,896 × 2,438 mm (20-ft container)
- Weight
- 40.3 ± 0.5 t
- Cooling
- Intelligent liquid-cooled
- Fire suppression
- Dry pipe · gas detection & ventilation · aerosol · alarm system
- Certificates
- IEC 62477-1 · IEC 62619 · IEC 63056 · IEC 60730 · IEC 61000-6-2/-6-4 · IEC 62933
Specifications from official Risen documentation. Always confirm against the current datasheet before specifying.
Downloads
Installers and distributors: product information for installers →
FAQs
Is it certified for Australian grids?
It is IEC-certified for 50 Hz grids including Australia, to IEC 62477-1, 62619, 63056, 62933 and more.
What conditions can it run in?
It is rated IP55 and from −30°C to +55°C, with intelligent liquid cooling to keep the cells in their optimal temperature band.
How do I source it for a project?
Talk to our team about project supply of the eTron 5 MWh: volumes, delivery schedule and documentation for your procurement.
Planning a grid-scale storage project?
Discuss project supplyInstaller or distributor? Access product resources